c machine. does not recover or tank refill. I replaced the spin on filter and compressor now I'm lost doing the same thing. Checked the recovery solenoid and its ok
Measuring Tools & Sensors - Robinair - Cool Tech 34700Z Recovery, Recycling, Recharging
Answers & Comments
Please check your machine ISV tank liquid hose,it's may lose or too tight
You can try the following :- 1# Verify the ISV tank is not overfilled.if full,remove refrigerant manually from tank. 2# Verify if there is high pressure in the tank.Purge excess air from the tank manually.( Open air purge hose from the tank,then press tank valve as needed)
2# Open Vaipor hose from ISV & connect again. make sure all the tank hose is not too tight or lose.
NOTE: if one of this three valve not connect properly the machin will not make recover or tank fill
You may need to change ISV tank,it seems to be contaminete. before you change ISV assy.just try with replace only VAIPOR & TANK LIQUID valve on ISV.
Also check High & Low side small recover solenoid (in small manifole assy.) it's may neet to rebuild.
Check Recover/Vacuum/charging (in main manifold assy.)solenoid,rebuild if need. Check high side coupler is opening properly.Hope this will help you to solve the problem