Central Air Compressor Runs Constantly
My Central Air unit will not stop running. The blower inside will kick off when the temperature gets down to the specified limit, which happens fairly quickly. The air coming out is very cold and appears to be working properly, but the Compress will only stop when I flip the breaker.
Heating & Cooling - Weather King - 10AJA2501AH Air Conditioner
Answers & Comments
Sounds like the contactor is stuck in the outside unit. Turn off the breaker or safety switch, remove the cover, and tap on the body of the contactor with a hammer handle or similar tool. If a click is heard you may have dislodged it and it may work for either a short time or indefinitely. (yeah ,I know that's kinda vague) Test it. If that doesn't clear it up, disconnect the thermostat wires just to make sure and re-test. If the compressor starts without the thermostat connected, you will need to replace the contactor. If you feel real handy, you could perhaps remove the cover, seperate the contacts with a screwdriver, dress the contacts with an emery board until smooth and shiny, and try again.