Central heater will not heat up to set temp on thermostac
The draft inducer blower is on all day, there is a red light in the ctrl panel when the burners come on, the burner will shut off when the blower fan comes on. will not reach temp. 70 I replaced the thermostat and cleaned the flame sensor. do i need to replace the flame sensor.
Tools & Hardware - Others - Omega - Trane Furnace Draft Inducer Blower 115 Volt Variable Speed...
Answers & Comments
Pressure port is plugged pull hose off draft motor and clean port with a paper clip