Just put in a new 3 ton system, compressor and outside fan won't start contacts are engaged. and it has power 120 both sides. The unit is a GSH 130361a
YOU CAN HAVE 120 ON EACH LEG WITHOUT HAVING 240 ACROSS CHECK ACROSS BOLTH LEGS.IF YOU HAVE 240 YOU PROBABLY HAVE A SAFETY HOLDING IT OUT.TRACE THE POWER FROM THE CONTACTOR THREW THE BOARD BY HOLDING ONE METER LEG ON COMMON AND WALKING THREW THE CIRCUIT WITH THE OTHER LEG.
Answers & Comments
YOU CAN HAVE 120 ON EACH LEG WITHOUT HAVING 240 ACROSS CHECK ACROSS BOLTH LEGS.IF YOU HAVE 240 YOU PROBABLY HAVE A SAFETY HOLDING IT OUT.TRACE THE POWER FROM THE CONTACTOR THREW THE BOARD BY HOLDING ONE METER LEG ON COMMON AND WALKING THREW THE CIRCUIT WITH THE OTHER LEG.
Safety switch or circuit board.