FREEZER. TRIPS CIRCUIT
TRAULSEN RDT232 REFIGERATOR/FREEZER. TRIPS THE CIRCUIT WHEN BOTH FRIDGE AND FREEZER ARE ON. WORKS FINE WITH ONE OR THE OTHER TURNED OFF. THE CIRCUIT IS DEDICATED AND MORE THAN SUFFICIENT TO HANDLE THE UNIT. ANY IDEAS??
Refrigerators - Traulsen - Commercial 2 Door Cooler / Refrigerator
Answers & Comments
Since you are convinced that the circuit is sufficient, look for a voltage drop during start up. In the unique case, when both units try to start at the same time, a voltage drop can cause overamping and trip the breaker.
Look at that and let me know if we need to go any farther