Generac control wires
The cable that came with the generac has 4 control wires in it. The connection block in the generator and the transfer switch has 6, am I missing something or do 2 wires not have to be connected?
Electrical Supplies - Generac - 100 Amp 120/240-Volt Transfer Switch #RTSN100A3
Answers & Comments
Older model Generac only haver 4 control wires:
N1
N2
23
194
if it is the included wiring harness the wires should have their numbers stamped on the jacketing and a sticker should designate the proper screw to mount it to in both the ATS and the generator housing. hooking these wires up incorrectly often results in blown fuses and/or damage to the control board in the generator.
Just 4. I install generac switches and generators
The 4 wire you have in the cable are utility sense and the start circuit. the two extra terminals that you are talking about are likely the battery charge circuit