Have not used the kegerator for several years. Plugged it in and it immediately started getting cold. Then I unplugged it to move it and when I plugged it back in it does not get cold
Check to see if any of the compressor electrical items came loose when moving. I had this happen to a customer and he called someone else in who tried to sell him a new compressor.
Check the fuse or circuit breaker for the outlet you now are plugging into.
Check for power at the outlet with a voltmeter, not test light or "hot-stick" as they tend to give false readings.
Example customer complained hid window a/c would not run he sais building maintenance checked outlet with "hot-stick" which showed good.
I tested with a volt meter and showed no voltage.
Outlet had broken neutral.Check the fuse or circuit breaker for the outlet you now are plugging into. Check for power at the outlet with a voltmeter, not test light or "hot-stick" as they tend to give false readings. Example customer complained hid window a/c would not run he sais building maintenance checked outlet with "hot-stick" which showed good. I tested with a volt meter and showed no voltage. Outlet had broken neutral.
Answers & Comments
Check to see if any of the compressor electrical items came loose when moving.
I had this happen to a customer and he called someone else in who tried to sell him a new compressor.
Check the fuse or circuit breaker for the outlet you now are plugging into.
Check for power at the outlet with a voltmeter, not test light or "hot-stick" as they tend to give false readings.
Example customer complained hid window a/c would not run he sais building maintenance checked outlet with "hot-stick" which showed good.
I tested with a volt meter and showed no voltage.
Outlet had broken neutral.