Hi! I need to rewire the electrical connection. I'm wondering if a 20amps electric break is enough. Does anyone knows how many amps does it takes set on 125 F?
Water Heaters - Rheem - 30 GAL ELEC SHORT Water Heater 6YR SC 82SV302
Hi, It does not matter what temperature you set it on it will still pull more then 20 amps. You will need to have a 30 amp. breaker and run 10 gauge wire to run a 4500 watt electric hot water heater. When it is on it always will pull the same amount of current no matter what the temp. of the water is or the thermostat setting...
Answers & Comments
Hi,
It does not matter what temperature you set it on it will still pull more then 20 amps. You will need to have a 30 amp. breaker and run 10 gauge wire to run a 4500 watt electric hot water heater. When it is on it always will pull the same amount of current no matter what the temp. of the water is or the thermostat setting...