How to adjust the Rated Motor Current in keb combivert f4-c. I cannot understand in manual
Hi i am working with Combivert F4-C and it is showing repeatedly E_OC and i checked the winding(Its Perfect). The motor is even running but the current peaks up even after extending acceleration time. Please Help
Electronics - Others - Inverter - KEB COMBIVERT F5
Answers & Comments
Run the motor with no load to see if it functions with no load.
If the system functions with no load, you may still need to increase your acceleration time to reduce the current demand.
What is the part# / serial# of the inverter in question?