I Have a beige goodman furnace (old ones) gmp... i replaced the circuit board..it worked fine..then once it reached its desire temprature from thermostat.. fire goes out then 2 min following is the blower motor..but inducer motor stays on and on.... so the house temprarture is droping and the furnace isnt starting???? Help please
Heating & Cooling - Goodman - CACF048B2A Air Conditioner
Check the pleum high limit switch. Jump this control out and see if the furance runs until the call for heat is satified. Do mot leave the high limit jumperd.
Answers & Comments
Check the pleum high limit switch. Jump this control out and see if the furance runs until the call for heat is satified. Do mot leave the high limit jumperd.