I have a daikin altherma after 5 mins of running it trips the RCD. The outdoor has its own RCD and the indoor is on its own RCD, it’s the indoor RCD that keeps tripping. I tested the compressor and found it had seized up so after swapping out the compressor and inverter board I thought this would have solved the problem. But was the system was recharged and run the same problem occurred, once I reset the RCD the LC-16 lower pressure sensor came up and was wondering if this would trip the breaker out on low pressure as it’s saying it faulty
Heating & Cooling - Inverter
Please enter comments
Please enter your name.
Please enter the correct email address.
You must agree before submitting.

Answers & Comments


Helpful Social

Copyright © 2024 QA.XPDF.PUB - All rights reserved.