KF9000e. Why does compressor cycle at short intervals?
Is cooling correctly. The compressor comes on and it blows cold air but the compressor kicks back off. It seems to continually kick off and on in short intravals.
Yes. due to low rpm of fan motor in the condensor copil. or dirty condensor coil. I If so, replace fan capacitor. If all good, check the seating of condensor set. It needs minimum 2mtrs open space for air throw. If not due to overheat compressor gets short cycling on and off.
Answers & Comments
Yes. due to low rpm of fan motor in the condensor copil. or dirty condensor coil. I If so, replace fan capacitor.
If all good, check the seating of condensor set. It needs minimum 2mtrs open space for air throw. If not due to overheat compressor gets short cycling on and off.