Look below I have a remmington kerosine space heater model 60.Starts runs fine for 10 mins ,then shuts off. up plug for a min. plug in and it will restart and run fro about 5 min. then shut off again...Any help?
Heating & Cooling - All-Pro - Kerosene Garage Shop Heaters - All Pro PK115T Forced Air...
Generally this means the heater is just in need of a tune up. There is a fuel filter where the fuel sucks out of the tank. The nozzle should be replaced and the air pressure should be adjusted to between 3.5 to 4 psi.
Pull out the fuel filter and backflush the filter with clean kerosene.Carefully remove nozzle and apply forced air into nozzle in the oppositelow direction of fuel fPull out the fuel filter and backflush the filter with clean kerosene.Carefully remove nozzle and apply forced air into nozzle in the oppositelow direction of fuel f
Answers & Comments
Generally this means the heater is just in need of a tune up. There is a fuel filter where the fuel sucks out of the tank. The nozzle should be replaced and the air pressure should be adjusted to between 3.5 to 4 psi.
Make sure air and fuel filter are clean.Set pump pressure to mfg set pressure after two minutes of operation
Pull out the fuel filter and backflush the filter with clean kerosene.Carefully remove nozzle and apply forced air into nozzle in the oppositelow direction of fuel f