Low Pressure Reset
When you turn on the machine, and don't even touch a button it will show a error message "HIGH PRESSURE RESET (ANY KEY EXITS)" Then it will reboot, the same message will appear. Then the third time a message that says, "LOW PRESSURE RESET (ANY KEY EXITS)" apprears. Then the system will continue to reboot.
I am currently deployed to Iraq and have only had this machine for about a month.
Measuring Tools & Sensors - Robinair - Cool Tech 34700Z Recovery, Recycling, Recharging
Answers & Comments
Your machine may need to Calibrate pressure transducer or replace new one.switch ON the machine (FOR MODEL 34700Z) & follow on screen message.You can also try the following:1# Check recovery solenoid (S1) coil & make sure it's not burne or it's may need to rebuild.if so,replace new coil/rebuild solenoid flunger.2# Check inlet low & high side solenoids (small solenoids S10-S11-S13-S14) is receiveng power & opening properly.Hope this will solve your problem
Model:34788 is the most complected machine of Robinair.However it's seems to be problem with your unit relay board or pressure transducer's.Most of Robinair 34788 machine having same problem.You can try as follows 1# Replace new relay board & follow the on screen message(Do not skip any option).3# Check pressure transducer is working properly.I hope this will help you.