Hello Btandpt let me tell you that the possible reasons for the problem you are currently facing are..
If you can get in, clean out the jet with a pin. Likelihood is the flame is only a fraction of what it should be, and isn't keeping the little safety valve open. call service engineer.
dirty pilot symptom yellow flame (lower temperature soot on thermocouple)
worn thermocouple symptom blueflame will not hold
faulty gas valve symptom as above more expensive to fix
faulty case seal goes out on windy day
vitiation lack of air, sooting, (boiler needs servicing gas boilers shoudn't ever soot).
lose t\c connection on gas valve
some boilers have a over heat swich in the t\c cuircut it may have tripped. why? maybe the pump or the thermostat etc etc as you say that thermocouple is new it does not mean that a new one is always Ok.. please do check it again.
Normal 0 false false false MicrosoftInternetExplorer4 /* Style Definitions */ table.MsoNormalTable {mso-style-name:"Table Normal"; mso-tstyle-rowband-size:0; mso-tstyle-colband-size:0; mso-style-noshow:yes; mso-style-parent:""; mso-padding-alt:0in 5.4pt 0in 5.4pt; mso-para-margin:0in; mso-para-margin-bottom:.0001pt; mso-pagination:widow-orphan; font-size:10.0pt; font-family:"Times New Roman"; mso-ansi-language:#0400; mso-fareast-language:#0400; mso-bidi-language:#0400;} Its better you replace the pilot lamp generator which is in the pilot assembly. It is the piece with a silver cable coming out of it and that cable splits open into a red and white wire at the gas valve, That piece holds the valve open once it is hot enough and is likely not putting out enough voltage to do its job. Millivolt models have a thermocouple or pilot generator that may be faulty or weak. Loose or rusty connections of the thermocouple to the gas valve or loose coil connection, or short in these wires can shut off a pilot
Sorry for error in connecting i'm only input again my sollution ;
Its better you replace the pilot lamp generator which is in the pilot assembly. It is the piece with a silver cable coming out of it and that cable splits open into a red and white wire at the gas valve, That piece holds the valve open once it is hot enough and is likely not putting out enough voltage to do its job. Millivolt models have a thermocouple or pilot generator that may be faulty or weak. Loose or rusty connections of the thermocouple to the gas valve or loose coil connection, or short in these wires can shut off a pilot
Good luck;
Sorry for error in connecting i'm only input again my sollution ;
Its better you replace the pilot lamp generator which is in the pilot assembly. It is the piece with a silver cable coming out of it and that cable splits open into a red and white wire at the gas valve, That piece holds the valve open once it is hot enough and is likely not putting out enough voltage to do its job. Millivolt models have a thermocouple or pilot generator that may be faulty or weak. Loose or rusty connections of the thermocouple to the gas valve or loose coil connection, or short in these wires can shut off a pilot
posible causes 1.dirty pilot symptom yellow flame (lower temperature soot on thermocouple) 2. worn thermocouple symptom blueflame will not hold 3. faulty gas valve symptom as above more expensive to fix 4. faulty case seal goes out on windy day 5. vitiation lack of air, sooting, (boiler needs servicing gas boilers shoudn't ever soot). 6. lose t\c connection on gas valve 7. some boilers have a over heat swich in the t\c cuircut it may have tripped. why? maybe the pump or the thermostat etc etc Also check .. http://www.letsfixit.co.uk/html/boiler_hints.html Thanks Kindly rate the answer Kevin
Answers & Comments
Hello Btandpt- If you can get in, clean out the jet with a pin. Likelihood is the flame is only a fraction of what it should be, and isn't keeping the little safety valve open. call service engineer.
- dirty pilot symptom yellow flame (lower temperature soot on thermocouple)
- worn thermocouple symptom blueflame will not hold
- faulty gas valve symptom as above more expensive to fix
- faulty case seal goes out on windy day
- vitiation lack of air, sooting, (boiler needs servicing gas boilers shoudn't ever soot).
- lose t\c connection on gas valve
- some boilers have a over heat swich in the t\c cuircut it may have tripped. why? maybe the pump or the thermostat etc etc as you say that thermocouple is new it does not mean that a new one is always Ok.. please do check it again.
let me tell you that the possible reasons for the problem you are currently facing are..
Normal 0 false false false MicrosoftInternetExplorer4 /* Style Definitions */ table.MsoNormalTable {mso-style-name:"Table Normal"; mso-tstyle-rowband-size:0; mso-tstyle-colband-size:0; mso-style-noshow:yes; mso-style-parent:""; mso-padding-alt:0in 5.4pt 0in 5.4pt; mso-para-margin:0in; mso-para-margin-bottom:.0001pt; mso-pagination:widow-orphan; font-size:10.0pt; font-family:"Times New Roman"; mso-ansi-language:#0400; mso-fareast-language:#0400; mso-bidi-language:#0400;} Its better you replace the pilot lamp generator which is in the pilot assembly. It is the piece with a silver cable coming out of it and that cable splits open into a red and white wire at the gas valve, That piece holds the valve open once it is hot enough and is likely not putting out enough voltage to do its job. Millivolt models have a thermocouple or pilot generator that may be faulty or weak. Loose or rusty connections of the thermocouple to the gas valve or loose coil connection, or short in these wires can shut off a pilot
Good luck;
Regards;
VOTIT
Sorry for error in connecting i'm only input again my sollution ;
Its better you replace the pilot lamp generator
which is in the pilot assembly. It is the piece with a silver cable coming out
of it and that cable splits open into a red and white wire at the gas valve,
That piece holds the valve open once it is hot enough and is likely not putting
out enough voltage to do its job. Millivolt models have a thermocouple or pilot
generator that may be faulty or weak. Loose or rusty connections of the
thermocouple to the gas valve or loose coil connection, or short in these wires
can shut off a pilot
Good luck;
posible causes
1.dirty pilot symptom yellow flame (lower temperature soot on thermocouple)
2. worn thermocouple symptom blueflame will not hold
3. faulty gas valve symptom as above more expensive to fix
4. faulty case seal goes out on windy day
5. vitiation lack of air, sooting, (boiler needs servicing gas boilers shoudn't ever soot).
6. lose t\c connection on gas valve
7. some boilers have a over heat swich in the t\c cuircut it may have tripped. why? maybe the pump or the thermostat etc etc
Also check ..