Powerware 9125 power problems
Powerware 9125 3000VA UPS will not power up long enough to make it through the self test. I am set up with 2 EBM modules as well as the internal batteries. Have been sitting for nearly two years in a dirty warehouse, although the inside electronics are very very clean and I see no fuses open. Obviously the batteries might be shot, but I have no other components to really test that, however, I would think that the Line AC light would still turn and blink on when I got Utility power. However it doesn't. Hit the power on button and it tries to boot, but turns off and immediately tries to reboot. On the off chance it does work the batteries must be shot because it never reaches battery mode. Just shuts off. Any ideas? Thanks in advance for taking the time!
Computers & Internet - Eaton - Powerware® 9125 UPS System
Answers & Comments
Most modern ups units will not start at all without the batt, so disconnect the extra packs beg, borrow some new or old good batt blocs same spec as the original internal ones, as this is just a test any set of batts that is just ok will do.
fit them to the ups unit and see if it will start. if it will then you will need to replace all the batt blocs in the whole system.
If it does not start then the ups is faulty.
If you are not happy fitting /working with batteries then get a tech to do this work for you, batteries are very dangerous, they are always live and need to be handled with care at all times.