Please check the following:1# For not filling ISV tank (internal storage vassel) Check tank fill solenois,it's may need to rebuild or replace.2# For not compleet recovery,Check & make sure your machine compressor haveing 13''HG suction.if not then you have to replace new compressor.3# Check 13'' vacuum sensor is working properly. NOTE:PLEASE CHECK FILTER CAPAICITY,BECAUSE EVERY 68Kg/150Lbs OF REFRIGERANT RECOVERY YOU MUST CHANGE SPIN-ON FILTER.
Answers & Comments
Please check the following:1# For not filling ISV tank (internal storage vassel) Check tank fill solenois,it's may need to rebuild or replace.2# For not compleet recovery,Check & make sure your machine compressor haveing 13''HG suction.if not then you have to replace new compressor.3# Check 13'' vacuum sensor is working properly.
NOTE:PLEASE CHECK FILTER CAPAICITY,BECAUSE EVERY 68Kg/150Lbs OF REFRIGERANT RECOVERY YOU MUST CHANGE SPIN-ON FILTER.