Confirm with a volt meter that you are getting the required voltage from the condenser fan motor contactor, load side of the contactor,which should be the same contactor as for the compressor. Is the comprssor coming on. If the compresor is coming on and the fan motor is'nt, than the fan motor or the run capcitor for the fan motor has failed.
Answers & Comments
Confirm with a volt meter that you are getting the required voltage from the condenser fan motor contactor, load side of the contactor,which should be the same contactor as for the compressor. Is the comprssor coming on. If the compresor is coming on and the fan motor is'nt, than the fan motor or the run capcitor for the fan motor has failed.