This is a common problrm of Robinair 34700Z / 347002k & 347112k series machine.so don't worry just do the following :- 1# Verify the ISV tank is not overfilled.if full,remove refrigerant manually from tank. 2# Verify if there is high pressure in the tank.Purge excess air from the tank manually.( Open air purge hose from the tank,then press tank valve as needed) 3#Check the high pressure switch for proper operation,if not then replace high pressure switch.Hope this will solve your problem, if so please vot for it
For hi pressure unit disabled, check the big pressure switch on top of the aluminium manifold,(3 pin pressure switch, but 2 wired) when i disconect 1 wire from a working machine it said High pressure unit disabled.
Answers & Comments
This is a common problrm of Robinair 34700Z / 347002k & 347112k series machine.so don't worry just do the following :- 1# Verify the ISV tank is not overfilled.if full,remove refrigerant manually from tank. 2# Verify if there is high pressure in the tank.Purge excess air from the tank manually.( Open air purge hose from the tank,then press tank valve as needed) 3#Check the high pressure switch for proper operation,if not then replace high pressure switch.Hope this will solve your problem, if so please vot for it
For hi pressure unit disabled, check the big pressure switch on top of the aluminium manifold,(3 pin pressure switch, but 2 wired) when i disconect 1 wire from a working machine it said High pressure unit disabled.