If the fans run we know it aint the defrost timer and you are getting power to the compressor so that means you have a wire done burned off one of the compressor terminals hopefully or ya might need a compressor. Probably just a burnt wire. These are pretty tough units. Diagram and run info
Partslist
If you need further help, reach me via phone at https://www.6ya.com/expert/dan_73bbd84fe1d95b61
If the temp control was bad the fans on the compressor compartment would not run and you would suspect it was open but it ain't cause the fan is running. Gotta be a burnt wore. I don't see no relay or capacitor in the circuit or I would suspent that.If the temp control was bad the fans on the compressor compartment would not run and you would suspect it was open but it ain't cause the fan is running. Gotta be a burnt wore. I don't see no relay or capacitor in the circuit or I would suspent that.