What would be causing Reverse cycle Inverter split system to leak? I have checked filters are clean and that there is no blockages of outdoor drainage hose?
Model No - CS-E24JKR Outdoor Unit - CU-E24JKR 3.20kw/14.6A 230-250V 50Hz R4104 Production Date 2009/10 The unit has been running on 21 degrees with the fan on 2 bars and the leak steady from underneath unit on right hand side now it also has leak on left hand side. The unit was run for roughly hour at a time then turned off, hasn't been run since started 2nd leak spot. Unit started playing up approx 1 week ago?
Heating & Cooling - Inverter
Answers & Comments
The accumulated water has no drain to flow through, and is backing up in the indoor unit. Find the source of the clogged drain, and your problem will disappear. If you are lucky, you can pour a little bleach or peroxide in the indoor unit's cooling coil and the chemical will eat your clog. Otherwise, mechanical cleaning may be necessary. Check your installation manual to see how your unit is supposed to be plumbed.